© 2013 UTC Fire & Security. All rights reserved. 1 / 2 P/N 3100124 • REV 08 • REB 30JAN13
Genesis Signal Master Module Installation Sheet
Description
The Genesis Signal Master Module provides precision
synchronization and independent horn control for Genesis
strobes and horns. It mounts on the back of the first appliance
on the notification appliance circuit. Model numbers are listed
below.
Table 1: Models
Description
Number
Genesis Signal Master [1]
ADTG1M, EG1M, G1M, MG1M, XLSG1M,
ZG1M
[1] This module is compatible with Genesi
s devices. For specific
models and quantities, see the compatibility list referenced on the
control panel.
The Signal Master Module only synchronizes appliances that
are electrically connected to, and electrically downstream from
it.
Installation
Install in accordance with applicable requirements in the latest
editions of the NFPA codes and standards and Canadian
Electrical Code, Part 1, Section 32, and in accordance with the
local authorities having jurisdiction.
To install the module:
1. Slide the spade connectors of the Genesis Signal Master
Module into the terminals on the back of the first Genesis
appliance on the notification appliance circuit. See
Figure 1.
2. Observing polarity, connect the wires for the remaining
appliances under the same terminals as the spade lugs.
See the wiring diagrams.
3. Connect the wires to the Genesis Signal Master. (See
Figure 2 through Figure 4).
Wiring
Only one Genesis Signal Master is required for each
notification appliance circuit.
The strobe input of the Genesis Signal Master requires a
dedicated NAC whereas the horn input of the Genesis Signal
Master can be cascaded with other Genesis Signal Master
modules on one NAC.
The strobe input source must supply a continuous 24 VDC
when active.
When determining allowable wire resistance, refer to the
voltage rating of the Genesis Signal Master Module, the
signaling appliance, and the control panel specifications.
Figure 1: Mounting the Genesis Signal Master Module
1. Genesis appliance
2. Genesis Signal Master Module
Figure 2: Synchronization using one NAC
1. From previous appliance or control panel
2.
Genesis appliance with Genesis Signal Master
3.
To next appliance, EOL resistor, or Class A circuit return. EOL
resistor value is determined by the control panel requirements.
4.
Jumpers: when using a single horn and strobe NAC circuit,
attach the NAC circuit to the bottom two terminals of the Genesis
Signal Master. Install jumper H− to S− and H+ to S+, as shown.
Notes
Polarity shown in alarm condition
The horns cannot be silenced without turning off the strobes
H
S
2
-
+
NAC_IN +
NAC_IN –
1
H
S
3
2
4
Vue de la page 0
1 2

Résumé du contenu

Page 1 - Installation

© 2013 UTC Fire & Security. All rights reserved. 1 / 2 P/N 3100124 • REV 08 • REB 30JAN13 Genesis Signal Master Module Installation Sheet Descr

Page 2 - STROBE_IN –

2 / 2 P/N 3100124 • REV 08 • REB 30JAN13 Figure 3: Horn silence / synchronization using two NACs 1. NAC 1 horn in 2. NAC 1 strobe in 3. Horn re

Commentaires sur ces manuels

Pas de commentaire