© 2013 UTC Fire & Security. All rights reserved. 1 / 4 P/N 3101058 • REV 02 • REB 25JAN13
FSRRM24 Remote Relay Module
Installation Sheet
Description
The FSRRM24 provides five Form C relays that you can
configure as common relays, zone relays, or as programmable
relays to use with F-series fire alarm control panels. In
addition, you can configure the relays as dry contact relays or
as 24 VDC output relays.
LEDs provide visual indication when each relay is energized
and when the FSRRM24 is disabled.
The FSRRM24 includes a plastic snap track for mounting in an
MFC-A cabinet.
FSRRM24 remote relay modules are configured using the
jumpers described in the tables below.
Table 1: Disable output jumper
JP1 Description
ON Disables all relays
OFF Enables all relays
Table 2: Module type jumpers
JP2 JP3 JP4 JP5 Description
ON OFF OFF OFF Five programmable relays (common
alarm or zone)
OFF ON OFF OFF Five zone relays (zones 6 to 10). This
setting is ignored on 3-zone and 5-
zone conventional F-Series control
panels.
OFF OFF ON OFF Five zone relays (zones 1 to 5)
JP2 JP3 JP4 JP5 Description
OFF OFF OFF ON Relay 1: Common alarm
Relay 2: Common trouble
Relay 3: Common supervisory
Relay 4: Common monitor
Relay 5: Common power
Note: Only one FSRRM24 module configured for common relay
operation is allowed per peripheral group.
Table 3: Group selection jumper
J6 Description
ON Selects peripheral group 1
OFF Selects peripheral group 2
Notes: Only three FSRRM24 modules are allowed per peripheral
group on 3- and 5-zone control panels. Only four FSRRM24 modules
are allowed per peripheral group on 10-zone control panels.
Table 4: Output selection jumpers, J1 to J5
Position Description
1 to 2 +24V output
2 to 3 Dry contact
Installation
Install the FSRRM24 according to the instructions provided
below.
Caution: Make sure all power is disconnected from the panel
before installing. Observe static-sensitive handling practices.
Vue de la page 0
1 2 3 4

Résumé du contenu

Page 1 - Installation Sheet

© 2013 UTC Fire & Security. All rights reserved. 1 / 4 P/N 3101058 • REV 02 • REB 25JAN13 FSRRM24 Remote Relay Module Installation Sheet Des

Page 2 - Snap track

2 / 4 P/N 3101058 • REV 02 • REB 25JAN13 Figure 1: FSRRM24 mounting To install the FSRRM24: 1. Mount the snap track on the MFC-A cabinet as show

Page 3 - Specifications

P/N 3101058 • REV 02 • REB 25JAN13 3 / 4 [3] If powered from an external supply, the supply must be installed in the same room as the control pan

Page 4

4 / 4 P/N 3101058 • REV 02 • REB 25JAN13